SAZAND

 

THE SAZAND RANGE OF MTU POWERED DIESEL GENERATING SETS

Ratings and Approximate unpacked dismensions

Model

Engine

Prime

Standby

Fuel Cons.

Length  (mm)

Width    (mm)

Height  (mm)

Net Wt. (Kg)

Packed Vol.(m3)

kVA

kW

kVA

kW

SPMTU277

6R1600G10F/70F

277

220

304

243

57

3200

1210

1800

2600

6.93

SPMTU300

6R1600G20F/80F

300

240

340

271

63

3200

1210

1800

2684

6.93

SPMTU350

8V1600G10F/70F

350

280

400

320

80

3200

1250

2050

3114

8.08

SPMTU400

8V1600G20F/80F

400

320

445

356

81

3300

1250

2050

3214

8.33

SPMTU450

10V1600G10F/70F

450

360

508

406

91

3520

1305

2050

3830

9.42

SPMTU500

10V1600G20F/80F

500

400

562

450

100

3520

1305

2050

3960

9.42

SPMTU593

12V1600G10F/70F

593

474

655

524

118

3620

1594

2130

4518

12.3

SPMTU655

12V1600G20F/80F

655

524

710

568

130

3620

1594

2130

4660

12.3

SPMTU773

12V2000G65

773

619

862

690

165

4200

1900

2250

5613

17.95

SPMTU908

16V2000G25

908

727

1000

800

189

4550

1900

2250

6497

19.45

SPMTU985

16V2000G65

985

788

1090

872

207

4550

1900

2250

6921

19.45

SPMTU1110

18V2000G65

1110

888

1237

990

238

4821

1900

2250

7371

20.6

SPMTU1262

12V4000G21R

1262

1009

1390

1112

258

4968

1800

2417

10510

21.6

SPMTU1360

12V4000G23R

1360

1088

-

-

276

4968

1800

2417

11068

21.6

SPMTU1615

12V4000G23

1615

1292

1840

1472

321

5204

1800

2417

11768

22.6

SPMTU1840

12V4000G63

1840

1472

2053

1643

358

5204

1800

2417

12006

22.6

SPMTU2020

16V4000G23

2020

1616

2300

1840

406

5950

2306

2650

14090

36.3

SPMTU2282

16V4000G63

2282

1826

2550

2040

442

5960

2306

2650

15505

36.4

SPMTU2565

20V4000G23

2565

2052

2825

2260

505

CONSULT US

SPMTU2840

20V4000G63

2840

2272

3095

2476

549

CONSULT US

SPMTU3041

20V4000G63L

3041

2433

3354

2683

585

CONSULT US

 

Notes:

1. All rating based on: 380V 3ph 50Hz power factor 0.8 and in accordance with ISO8528-1 and ISO3046, BS5514 and DIN6271 conditions

2. Fuel consumption figures are in liters per hour at 100% full load.